A Step by Step Guide to Maximizing your Brewery Tasting Room Occupancy – Part 2 of 4

Mixed Use and Occupancy; How to understand occupancy separations

In my last post How to define your room occupancy classifications we simply defined brewery occupancies by room. In this post I will discuss how the different occupancies relate to each other.

Defining Mixed Use and Occupancy

“Each portion of a building shall be individually classified in accordance with Section 302.1. Where a building contains more than one occupancy group, the building or portion thereof shall comply with the applicable provisions of Section 508.2, 508.3 or 508.4, or a combination of these sections.”

Under Section 508.1 of the 2010 CBC we can find Mixed Use and Occupancy which is generally defined, and with more detail under subsequent sections. Let’s take a look at Table 508.4

The table defines how the different occupancies relate to each other for buildings equipped throughout with an automatic sprinkler system (S) or buildings not equipped throughout with an automatic sprinkler system (NS). When Reading the table the dashed lines indicate where not to look. You must only look at the area’s that have a reference. Here are the separations for a typical craft brewery operation:

Brewery; Group F-2 > Tasting Room; Group A-2 no separation required for sprinklered and one hour separation for non-sprinklered.
Brewery; Group F-2 > Office; Group B one hour separation for sprinklered and two hour separation for non-sprinklered.
Office; Group B > Tasting; Room Group A-2 one hour separation for sprinklered and two hour separation for non-sprinklered.

This is the point at which we can analyze our results and start to make some very easy observations. We can clearly see that a fully sprinklered building will give us a reduction in our separations. So, when looking for a space for your start up brewery, having a building that is fully sprinklered can help to reduce your occupancy separations, but this is not the only factor to consider. If choosing a fully sprinklered building considerable costs can be associated with extending those systems to new rooms or areas.

Exceptions

With further analysis of the 2010 CBC we can find other ways to reduce our occupancy separations. In Section 508.2 we can take ten percent of the building area and create an accessory occupancy that is ancillary to the main occupancy. We can apply this to the Tasting Room; Group A-2, and Offices; Group B occupancies. Under Section 508.2.4 no separation is required between accessory occupancies and the main occupancy.

When applying accessory occupancies, Section 303.1 3 then reduces our A-2 occupancy to a B occupancy. Why this is important? Well, we will discuss that when we calculate our occupancy load for the Tasting Room and bathroom fixture counts.

Special note: Exceptions 303.1 1 and 2 can also be used if your determined occupant load is less than 50 occupants.

Using an example brewery of 5,000 sq. ft. We can now have a possible office that is 100 sq. ft. and a Tasting Room that is 400 sq. ft. You can balance those rooms as needed.

We all know that there are other types of rooms in a brewery operation. Take a look at Section 508.2.5 it describes incidental accessory occupancies and their separations. For breweries with steam boilers a one hour fire separation is required unless you have an automatic sprinkler system. Just remember to account for any costs to extend that system.

Thoughts

With some understanding we have determined what our occupancy separations are and how to reduce them by applying exceptions. When looking for a building to build you first or next brewery take these thoughts into consideration. You might want to get a building that is fully sprinklered to reduce your occupancy separations and or you might want a building with bigger square footage so that you can have a larger Tasting Room and, or Office spaces.

What do you think about this guide? Let us know in the comments below.

About Neil Rubenstein

Neil Rubenstein joined Rubenstein Architects in 2004 as co-founder of this second-generation architectural firm. With an extensive background as a Senior Technical Director in Visual Effects working for industry leading studios as, Sony Imageworks, Warner Digital, my vision for the firm is to blend my past experience creating buildings that possess a subtle character and personality of their own.

Comments (4)

  • Dylan Goldsmith August 2, 2015 - 4:26 pm Reply

    Could the brewery attached to a small (<50) tasting room/pub in an unsprinkled building get away without a firewall? Could it be considered a commercial kitchen to the tasting room?

    • Neil Rubenstein August 3, 2015 - 12:45 pm Reply

      Hi Dylan,

      Under Section 508.2.4 no separation is required between accessory occupancies and the main occupancy provided that the “Tasting Room” is less than 10% of the total area of the main occupancy. Essentially we do this all the time, it’s just a balance between accessory floor area, and occupancy load. Let me know your thoughts.

  • Jason Senior January 29, 2017 - 8:14 pm Reply

    Hi,
    Thank you for the information. We are located in a building with sprinklers. Can we have a f2 occupancy (brewery) with no fire separation from our A occupancy tasting room, then have our f1 (distillery) the 10% accessory space?

  • Lisa Dall'Olio November 29, 2017 - 1:54 pm Reply

    I understand that these are IBC separation requirements. The NFPA separations between Restaurant and General Industrial require 2 hours with a reduction to 1 with sprinklers. Any way around this?

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.